Introduction LW48100 (LiWATT 48V-100Ah & 48V-200Ah) is a communication lithium battery based on innovative Li-ion technology. It is specially designed for telecom sites with advanced features: a long…
Specification | Model | LW 48100 | |
---|---|---|---|
Electrical Characteristics | Nominal Voltage | 48V | |
Nominal Capacity | 100Ah | ||
Energy | 4800Wh | ||
Internal Resistance | ≤20mΩ( without BMS) | ||
Cycle Life | ≥4000 cycles @80%DOD | ||
Design Life | ≥15 years @25℃ | ||
Self-Discharge (30 days) | ≤3% @35℃ | ||
Efficiency of Charge | ≥98% | ||
Efficiency of Discharge | ≥100% @ 0.2C, ≥96% @ 1C | ||
Charge | Charge Voltage | 52.5-54.0V | |
Charge Mode | 0.2C to 54V, then 54V charge current to 0.02C (CC/CV) | ||
Max. Charge Current | 1C | ||
Discharge | Max. Continuous Discharge Current | 1C | |
Discharge Cut-off Voltage | 42.5V±0.5V | ||
Environmental | Charge Temperature Range | -20℃~60℃ (extra heating mechanism under 0oC) | |
Discharge Temperature Range | -20℃~60℃ (reduced capacity under 0oC) | ||
Optimum Operation Temperature | 10℃~35℃ | ||
Storage Temperature | -20℃~55℃,≤85% Relative Humidity | ||
Water Dust Resistance | IP20 | ||
Mechanical | Max. Weight | ≥41kg | |
Dimensions W*D*H (excluding hanger and handle bar) | 442*450*156mm | ||
Case | Iron (Insulation painting) | ||
Min. Gravimetric Specific energy | 112Wh/kg | ||
Terminal | M6*2 for positive and M6*2 for negative | ||
Parallel in maximum | 16pcs in maximum, vertical or horizontal install are both allowed | ||
Communication | Parallel Communication | RS485 | |
Battery with Equipment | RS485 | ||
Battery Debugging Communication | RS232 | ||
SOC Light | 4 * LED | ||
Charge Current limit | When the charging current exceeds the set value, turn on the current limit and limit the current to 10A | ||
Optional Functions | LCD Screen | |Yes: Displays the total voltage pack, cell voltage, temperature, BMS status, etc. | No | |
Gyroscope anti-theft | | Yes Keep battery tilt more than 15° to turn on anti-theft | No | ||
Buzzer | | Yes | No | ||
Dry Contact | | Yes PIN1 to PIN2: Normally closed, open during low power PIN3 to PIN4: Normally closed, open during fault protection | No |